Indoor Air Quality Monitoring: What CO₂, TVOC and PM Each Tell You — and How to Measure Them
"CO2 above 1,000 ppm means bad air" — half industry consensus, half the most widespread misconception in the field. ASHRAE's official position paper states flatly that Standard 62.1 has never set a 1,000 ppm limit. This article splits IAQ monitoring into three different jobs — CO₂ for ventilation, TVOC for pollution sources, PM for particulates — lays out the full GB/T 18883-2022 limit table, and explains which sensor principle fits each layer, where to mount it, and how to interlock it with ventilation.
- 0.10% GB/T 18883 indoor CO₂ limit (1-h mean)
- 0.60 mg/m³ GB/T 18883 TVOC limit (8-h mean)
- ≥30 m³/h GB/T 18883 minimum outdoor-air rate per person
- 800 ppm EN 16798-1 Category II: CO₂ above outdoor
First, correct the most widespread misconception
Many believe ASHRAE 62.1 caps indoor CO₂ at 1,000 ppm. ASHRAE's Position Document on Indoor Carbon Dioxide says otherwise: Standard 62.1 has never set an indoor CO₂ limit; misread text from earlier editions let the "1,000 ppm limit" circulate for decades. The real origin: 1,000 ppm corresponds to the level of body-odour acceptability at roughly 8 L/s of outdoor air per person — a ventilation-rate indicator, not a health threshold.
The European standard EN 16798-1 is clearer: it grades CO₂ above the outdoor baseline into four categories — Cat I 550 ppm, Cat II 800 ppm, Cat III/IV 1,350 ppm — each mapping to a different per-person outdoor-air expectation. Note these are differentials: outdoor baseline now commonly runs 420–500 ppm and must be factored in; comparing indoor absolute readings against an old table misjudges the result.
GB/T 18883-2022: the whole limit table
The Chinese national standard GB/T 18883-2022, effective February 2023, is the benchmark for indoor air assessment in residential and office buildings. The monitoring-relevant chemical and physical parameters are set out below.
- Construction acceptance is governed separately by GB 50325, whose Class I civil buildings (dwellings, hospitals, schools) carry a stricter formaldehyde limit of 0.07 mg/m³. For project-bound monitoring, confirm first which standard the client is being accepted against.
- GB/T 18883's reference methods are laboratory methods: TVOC by Tenax-tube sorption, thermal desorption and GC; formaldehyde by spectrophotometry. Online sensor readings do not replace a CMA report — they carry the continuous-trend and early-warning role, complementary to periodic lab testing.
| Parameter | Limit | Averaging |
|---|---|---|
| Carbon dioxide CO₂ | ≤ 0.10 % by volume (≈1000 ppm) | 1 hour |
| TVOC | ≤ 0.60 mg/m³ | 8 hours |
| Formaldehyde HCHO | ≤ 0.08 mg/m³ | 1 hour |
| Fine particulate PM2.5 | ≤ 0.05 mg/m³ (50 µg/m³) | 24 hours |
| Inhalable particulate PM10 | ≤ 0.10 mg/m³ | 24 hours |
| Carbon monoxide CO | ≤ 10 mg/m³ | 1 hour |
| Ozone O₃ | ≤ 0.16 mg/m³ | 1 hour |
| Outdoor air rate | ≥ 30 m³/(h·person) | — |
The CO₂ layer: why NDIR is the only sound principle
The mainstream CO₂ principle is non-dispersive infrared (NDIR): CO₂ characteristically absorbs 4.26 µm infrared light, and the more there is, the more is absorbed. It is specific to CO₂, free of cross-interference and long-term stable — which is why decades have produced no replacement. Three things to check when specifying: range (0–5,000 ppm is ample for IAQ — avoid personal-safety 0–5% Vol tiers), automatic baseline calibration (ABC, which self-zeroes on periodic exposure to fresh outdoor air — be careful with ABC in rooms that are never opened up), and the temperature-drift spec.
Placement trips people up more than selection: CO₂ is not uniform in a room — occupied zones, ventilation dead corners and return grilles can differ by hundreds of ppm. Mount at breathing height in the densely occupied zone (about 1.1–1.2 m for seated work), away from doors, windows and supply-air jets; one sensor represents one ventilation zone, and open-plan floors need multiple points per zone.
CO₂-driven ventilation: the savings beyond safety
Demand-controlled ventilation (DCV) is where a CO₂ sensor earns its keep: a seated adult exhales roughly 18–19 litres of CO₂ per hour, and with adequate ventilation the room settles at "outdoor baseline + G/Q" (G the generation rate, Q the outdoor air per person). In spaces with swinging occupancy — meeting rooms, classrooms, dining halls, cinemas — fixed-rate ventilation sized for peak occupancy massively over-ventilates off-peak. Closing the loop from a CO₂ sensor onto dampers or fan speed typically returns 20–40% of ventilation energy in classrooms and meeting rooms while never under-delivering at peak.
A 2023 addendum to ASHRAE 62.1 recast the DCV control value as a maximum differential above ambient, converging with EN 16798-1's category approach — which in turn means DCV set-points must be anchored to the local outdoor baseline, not one national number.
The TVOC layer: realistic online practice
TVOC spans hundreds of compounds between n-hexane and n-hexadecane, emitted by materials, furniture, cleaners and printers — independent of headcount. So it measures sources, complementing CO₂'s measurement of ventilation. The reference method is laboratory GC (8-hour mean); online sensors take the equivalence route — electrochemical or MOS elements responding to the VOC mixture as a total reading for continuous trend and early warning.
Two realities at selection: first, an equivalence TVOC reading (in mg/m³ or ppm, calibrated on e.g. isobutylene) is not strictly comparable with the GC method's toluene-equivalent mg/m³ — compliance calls still need lab sampling; second, sensors respond weakly to high-boiling compounds, and formaldehyde must be measured with a dedicated element — a normal TVOC reading does not certify formaldehyde compliance.
For particulates, laser-scattering PM2.5/PM10 monitors are mature online; just separate cleanroom-grade from everyday IAQ-grade accuracy needs. For the CO layer (premises with combustion appliances), apply the occupational/indoor limits from our CO monitoring article. With that, every layer sits in place: CO₂ → ventilation, TVOC → sources, PM → particulates, plus dedicated CO and formaldehyde where applicable.
Frequently asked questions
At what indoor CO₂ level is the air out of compliance?
Where should the CO₂ sensor be mounted?
Can a TVOC sensor reading be compared directly with the national limit?
Is a 5-in-1 module (CO₂/HCHO/PM/T-RH) worth it?
Sources
GB/T 18883-2022 (Chinese indoor air quality standard); GB 50325-2020 (indoor environmental pollution control for civil building engineering); ASHRAE Position Document on Indoor Carbon Dioxide (2022); EN 16798-1:2019; ASHRAE Standard 62.1-2022 incl. 2023 addendum; WHO Global Air Quality Guidelines (2021)